June 2010

Volume 19, Number 6

Get the PDF

By downloading this digital content, you agree to BuildingGreen’s terms and conditions of use.


Article Contents

Avoiding the Global Warming Impact of Insulation

Printer-friendly versionSend to friend

By Alex Wilson

Insulation is key to reducing carbon emissions from buildings. But the blowing agents in extruded polystyrene and spray polyurethane foam offset much of that benefit.

Benson.jpg

Unaware of the recently reported GWP implications of certain foam insulation materials, builder Tedd Benson specified four inches of extruded polystyrene over 2x6 studs insulated with dense-pack cellulose in this net-zero-energy home.

Photo: Bensonwood

Two common foam insulation materials are produced with hydrofluorocarbon (HFC) blowing agents that are potent greenhouse gases— extruded polystyrene (XPS) such as Dow Styrofoam of Owens Corning Foamular, and standard closed-cell spray polyurethane foam (SPF). While all insulation materials reduce greenhouse gas emissions (by saving energy), insulating with thick layers of either of these two particular foams results in very long “payback periods” for the global warming potential of the insulation, thwarting even the best attempts to create carbon-neutral buildings. The bottom line is that designers and builders aiming to minimize the global warming impacts of their buildings should choose fiber insulation (cellulose, fiberglass, or mineral wool) or non-HFC foam insulation.

“The more insulation the better” is a common refrain in the green building industry. EBN has long advocated very high levels of insulation, particularly in residential and small commercial buildings, which are skin-dominated. At the furthest end of the spectrum is the Passive House movement (see EBN Apr. 2010), where it is not uncommon to provide R-50 under a floor slab, R-60 in the walls, and as much as R-100 in the attic. High levels of insulation are seen as a key strategy for achieving net-zero-energy and carbon-neutral performance—the latter meaning that the building will have no net contribution to climate change.

How we achieve high levels of insulation is a very significant issue, however. We rarely pay attention to the fact that insulation materials themselves contribute to greenhouse gas emissions and global warming. This happens in two ways: through the embodied energy of the insulation (the energy use and greenhouse gas emissions that result from manufacturing and transporting the material); and, with some foam insulation materials, through the leakage of blowing agents that are highly potent greenhouse gases.

Understanding Embodied Energy and GWP

Researcher Danny Harvey, Ph.D., of the University of Toronto, sounded the alarm about the climatic impacts of blowing agents used in certain foam insulation materials in a technical paper in the August 2007 issue of the journal Building and Environment. Daniel Bergey of Building Science Corporation presented a synopsis of Harvey’s research at the Northeast Sustainable Energy Association (NESEA) Building Energy Conference in March 2010.

With the help of Bergey and John Straube, Ph.D., P.Eng., of Building Science Corporation, EBN reexamined the assumptions Harvey used, included new information about the blowing agents in use today (which differ from what Harvey assumed), and calculated the payback on the lifetime global warming potential (GWP) of insulation materials.

All insulation materials take energy to manufacture and transport—something we refer to as embodied energy. We consulted the Inventory of Carbon and Energy (ICE), developed by Geoff Hammond and Craig Jones of the Department of Mechanical Engineering at the University of Bath in the U.K., for values of embodied energy and embodied carbon for different insulation materials. Although its figures are based on European (rather than North American) data on the energy used to produce and transport building materials, ICE offers the most accessible, current information available on embodied energy. Using this data and information about insulation performance, we can calculate the embodied GWP of these insulation materials. Currently, ICE does not address blowing agents.

Blowing agents

Table 1. ODP and GWP Values of Blowing Agents Used in Foam Insulation

blowing_agents.gif

When insulation materials are made with halocarbon blowing agents (compounds containing halogens, such as chlorine or fluorine), the GWP of those gases far outweighs the embodied GWP that results from the embodied energy of the insulation materials.

Blowing agents create tiny bubbles of low-conductivity gas in closed-cell foam insulation materials. Chlorofluorocarbons (CFCs) were originally used as blowing agents for polyisocyanurate (polyiso), extruded polystyrene (XPS), and closed-cell spray polyurethane foam (SPF). After it was discovered in the 1970s and ’80s how damaging CFCs are to the Earth’s protective ozone layer, they were replaced with “second-generation” hydrochlorofluorocarbon (HCFC) blowing agents, which had lower ozone depletion potential (ODP), as required by provisions of the Montreal Protocol on Substances That Deplete the Ozone Layer.

These second-generation HCFC blowing agents were required by the Montreal Protocol to be phased out at the beginning of 2010; some have been replaced with “third-generation” HFC blowing agents. While these HFCs have zero ozone depletion potential, they are quite potent greenhouse gases. Initially, there was little focus on this property of halocarbon blowing agents, but concern about GWP of foams is growing. Blowing agents used in common foam insulation materials—both historically and today—are shown in Table 1.

Lifetime GWP of insulation materials

Table 2. Lifetime GWP of Common Insulation Materials

embodied_GWP.gif

By combining information about the GWP of the blowing agent in foam insulation (the quantity used in the foam and assumptions about how much leaks out over time) with the embodied GWP based on the embodied energy, we can calculate the lifetime GWP of an insulation material. Lifetime GWP is presented in Table 2. The data in this table has been normalized by square-foot R-value (far right column) to provide a common basis for comparison. Note that the values are highly dependent on assumptions; we chose conservative assumptions—key among them the assumption that 50% of the HFC blowing agent in foam will never leak out over the lifetime of the insulation. (Harvey assumed more rapid loss of blowing agents in his analysis.) In our analysis, we don’t address the rate of loss, per se, only that 50% of the gas will leak out over its lifetime—which could be 50 years or 500 years; what happens to the foam during disposal has a significant effect on whether the blowing agent is released into the atmosphere. There is currently very little information on the lifetime of blowing agents in foam insulation; we hope that the U.S. Environmental Protection Agency or manufacturers will conduct research on this issue, which has tremendous bearing on the lifetime GWP of insulation materials.

Calculating GWP payback

Figure 1. Lifetime GWP Payback XPS & SPF

GWP_chart1.jpg

The lifetime GWP payback of extruded polystyrene (XPS) and standard closed-cell spray polyurethane foam (SPF), both of which are produced with HFC blowing agents, compared with other insulation materials. The analysis assumes that 50% of the blowing agent is lost over the life of the material.

The next step is calculating the “payback” of the lifetime GWP in insulation materials. By reducing heat loss and unwanted heat gain, any insulation material reduces the use of fossil fuels or electricity required for heating and cooling buildings. In so doing, these insulation materials reduce emissions of carbon dioxide (CO2), a greenhouse gas that contributes to global climate change. We want to know how many years of energy savings it will take to pay back the lifetime GWP of the insulation to figure out whether it’s a good idea to use that insulation material in our low-energy buildings. Another way to think about this is how many years of energy savings will be required to “break even” on the GWP of the insulation.

In Figure 1 and Figure 2, we have plotted this GWP payback of various insulation materials. These calculations are climate-specific and based on computer modeling. The graphs show the payback of the lifetime GWP of different insulation materials plotted as a function of final R-value in the moderately cold climate of Boston. We assume that heat is provided by a 90%-efficient gas furnace, and we do not account for any change to airtightness as a result of adding insulation. To provide a consistent basis of comparison, we assume that the insulation in question is added to a 2x6 wall insulated with fiberglass insulation (whole-wall R-value of R-14). This is a common application for foam insulation materials, though not for fiber insulation materials, such as fiberglass and cellulose.

Figure 2. Lifetime GWP Payback – Other Insulation

GWP_chart2.jpg

The lifetime GWP payback of various non-HFC insulation materials shown at a scale allowing comparison. In this analysis, closed-cell, water-blown SPF and rigid mineral wool are nearly identical, so those graphs cannot be distinguished.

The results show, first of all, that the GWP payback is very rapid for all insulation materials that are produced without HFC blowing agents. In adding R-25 of polyiso (about 4 inches) to an insulated 2x6 wall, for example, the payback of the lifetime GWP of the polyiso is about 2.7 years; going all the way to R-60 with 7.5 inches of polyiso would increase that GWP payback to only slightly over 4 years. With cellulose, the GWP payback is always less than one year, even at R-60.

With XPS and standard closed-cell SPF (produced with HFC-245fa), the GWP payback is much longer. With one added inch of XPS (R-5) the GWP payback is about 36 years; with two inches, the payback is 46 years; and with four inches the payback jumps to 65 years. Adding the same R-value increments of standard closed-cell SPF yields GWP paybacks of 30, 38, and 54 years respectively. (Because the R-value per inch of this SPF is somewhat higher than R-5/inch, those GWP paybacks result from somewhat thinner layers.)

Assumptions are key in this analysis. In a climate colder than Boston’s, the energy savings from the insulation will be greater, so the time required to pay back the lifetime GWP of the insulation will be shorter. In a warmer climate, the payback will be longer. If we were to assume that 100% of the HFC blowing agent leaks out over the life of the insulation, the payback periods of XPS and standard SPF would nearly double.

What This Means for the Way We Build

EBN spoke with several environmentally concerned designers and builders about the issue of GWP payback of insulation materials. Even though it’s a complex and confusing issue, we found that interest is strong (at least among this subset of the building industry), and the information could significantly change building practices.

According to Scott Shell, FAIA, a principal at EHDD Architecture in San Francisco, “combating global warming is the most critical issue, and specifying a high-GWP insulation completely defeats the point of using it.” Shell told EBN that he had become aware of this issue and his company is “moving aggressively to eliminate these [HFC-blown foams] on all of our projects.”

“This information will influence our product selection profoundly,” says David Foley, of Holland and Foley Architecture in Northport, Maine. “We do what we do for many reasons, but anthropogenic climate change is among the most important,” he told EBN. “Talk about an inconvenient truth!”

Larry Strain, FAIA, of Siegel & Strain Architects in Emeryville, California, told EBN that this information “will definitely influence our product selection.” His company has already started eliminating foam insulation from its projects because of concerns about halogenated flame retardants. “If it takes up to 60 years to recover the GWP from manufacturing the foams,” he said, “it gives us another, even stronger, reason to find alternatives.”

Nico Kienzl, of the environmental design consulting and lighting design firm Atelier Ten in New York City, told EBN that his firm has looked qualitatively at embodied energy and GWP in the past, and that has influenced what the company recommends (“our preferred choice being mineral wool”). “More quantitative information will be valuable in informing a discussion that often seems to be too single-mindedly focused on more insulation being always better,” Kienzl said.

Straube_EPS.jpg

John Straube used a tongue-and-groove EPS instead of XPS for insulating beneath the concrete slab in a deep-energy retrofit of his home.

Photo: John Straube

Shell says that “there are reasonable replacements in the vast majority of cases: polyiso for roof insulation, dense-pack cellulose or low-density spray foam (such as Icynene) instead of high-density, and rigid mineral fiber for walls above and below grade.” There remain some challenges, according to Shell. “We still need to look into finding suitable products for plaza deck insulation, where paver pedestals need good structural bearing capacity; and similar for below slabs-on-grade.”

EHDD just vetoed closed-cell spray foam for a Passive House the company is designing. “We’re using Icynene in the framed floor over a crawl space, and dense-pack cellulose in walls and ceilings,” said Shell. Rather than relying on SPF for air sealing on walls, Shell is sealing the joints of exterior sheathing with a self-adhered flashing, such as Vycor (from Grace Construction Products). “This is a better and cheaper approach than trying to use spray foam as an all-in-one solution,” he said.

EHDD also recently eliminated XPS from the Packard Foundation net-zero-energy office building the company is designing,“ due to high GWP and toxics.” In its place, the company is specifying Roxul mineral wool (see EBN Oct. 2009) both above and below grade.

On its Yosemite Institute project, Siegel & Strain Architects has eliminated almost all foam, except under slab and slab edge. “We may take another look at that now as well,” says Strain.

Tedd Benson, president of Bensonwood in Walpole, New Hampshire, and a well-known leader in the timber-frame construction field, has been refining insulation systems for decades. “We have been trying to make our production more efficient and simultaneously improve the performance and environmental characteristics of our wall and roof systems,” Benson told EBN. The company’s current wall system—the OBPlus Wall—is the latest in that evolutionary process, relying entirely on cellulose insulation between wood I-studs. “We didn’t have the benefit of your research when we developed the OBPlus Wall,” says Benson, “but I was happy to see that we look even wiser now than we thought we were.” The company’s foam insulation decisions are focused on the use of SIPs on some of its roof assemblies and below-grade requirements. “Your article will definitely guide us toward better decisions in these areas.”

Paul Eldrenkamp, of the residential remodeling company Byggmeister, in Newton, Massachusetts, and a Passive House consultant, had already been moving away from SPF when he heard Daniel Bergey’s presentation at the NESEA Building Energy conference. He had done this for three reasons:

First, spray foam (open-cell certainly, but also closed-cell) is much harder to install well than most people realize. We only began to understand this after we started testing every insulation job with a blower door. Second, installers do not protect themselves anywhere near well enough from the side effects of frequent exposure to the material before it’s fully cured. And third, the high fossil fuel content probably means the price of spray foam will track the price of petroleum, whereas cellulose, for instance, will likely always be a fraction of the cost of spray foam for a given R-value—so we shouldn’t forget how to insulate with cellulose.

Eldrenkamp notes that his company still does use a small amount of closed-cell SPF for strategic air sealing. “We believe that CCSF [closed-cell SPF] is uniquely effective and appropriate in old basements,” he told EBN. “We have done one deep-energy retrofit in which we sprayed CCSF on the exterior cladding before adding new cladding; we’ve decided that, going forward, we’ll strip the cladding and apply rigid PIR [polyiso] instead.”

Other Concerns With XPS and SPF

Along with the global warming potential of the HFC blowing agents in XPS and standard closed-cell SPF, there is also the issue of flame retardants. All foam insulation materials today are made with halogenated (chlorine- or bromine-based) flame retardants, and there is increasing concern about the health and environmental impacts of these compounds (see “Polystyrene Insulation: Does it Belong in a Green Building?” in EBN Aug. 2009 and “Flame Retardants Under Fire” in EBN June 2004).

If we replace HFC-blown foam insulation materials with fiber insulation alternatives, such as dense-pack cellulose installed in double-wall or Larsen-truss (curtain-truss) wall system, we can avoid the use of halogenated flame retardants. We can also continue pushing for foam insulation manufacturing to shift to safer, phosphorous-based flame retardants and composite manufacturing with layers that are fire-proof. While the foam insulation industry is transitioning to blowing agents that do not contribute significantly to global warming, it should also focus on addressing this other concern.

Other issues with SPF are quality control during installation and potential performance problems, particularly with the relatively new water-blown alternatives to HFC-blown SPF. With SPF insulation, the installer is essentially manufacturing the insulation in place. The process involves precisely mixing two components at the right temperatures and allowing the material to expand and cure (a process that uses water vapor from the air). Because curing SPF is an exothermic (heat-generating) reaction, manufacturers recommend installing no more than two inches (50 mm) at one time—and this is very hard to control, particularly in a cavity between framing members that are close together. If the foam builds up significantly thicker than two inches, there is potential for problems, such as offgassing of harmful chemicals or improper adherence or shrinkage. In short, proper installation of SPF requires a highly skilled installer and, even then, there are risks of performance and offgassing problems that are not well understood.

The Future of Foam Insulation

Manufacturers are working to develop and deploy fourth-generation blowing agents that have zero or very low GWP while still providing the various performance and safety properties that are required. Such developments would alter the conclusions of this article. Both Dupont and Honeywell are working on hydrofluoroalefin (HFO) blowing agents. At the 2010 NESEA Building Energy Conference, Gary Loh of DuPont described a zero-ODP, low-GWP (less than 10), nonflammable, low-conductivity blowing agent, for SPF, FEA-1100, that is currently undergoing toxicity testing and should be introduced (if toxicity testing continues to demonstrate safety) sometime between 2013 and 2015. Honeywell already has a similar product on the market in Europe for one-component polyurethane foams (HFO-1234ze) and expects to broaden its family of HFO blowing agents.

When these new products replace the HFC-blown insulations in the coming years, the argument for avoiding SPF and XPS on the basis of lifetime GWP should largely disappear. By then, manufacturers may also have replaced the halogenated flame retardants with safer compounds. Until that time, however, there are good reasons to limit use of XPS and closed-cell SPF.

Final Thoughts

Avoiding High-GWP Insulation Materials

materials.gif

If our goal is to create buildings that have little or no net contribution to global warming, then the lifetime GWP of insulation materials is a key consideration. When designing highly insulated buildings or carrying out deep-energy retrofits (a top priority of green building and renovating), we should avoid insulation materials with high GWP—extruded polystyrene and spray polyurethane foam that is made with HFC-245fa—so that we aren’t sacrificing the very environmental benefits we’re trying to achieve.

Furthermore, the GWP of foam insulation materials is high enough (especially earlier-generation materials made with CFCs and HCFCs) that it may even make sense to consider the capture and thermal degradation of these blowing agents during building demolition. In the early 1990s, Northeast Utilities in Connecticut had a program to recover and thermally destroy the CFC blowing agents in the polyurethane insulation recovered from refrigerators that were turned in through an appliance rebate program. That program was implemented to prevent ozone depletion, but such a program could apply as well to greenhouse gas emissions. Most of the XPS, SPF, and even polyiso currently in place was produced with CFC or HCFC blowing agents with significantly higher GWP values than today’s blowing agents, so there are considerable quantities of high-GWP foam “banked” in existing buildings, even accounting for leakage over the years.

As we consider alternatives to XPS and standard SPF, we should try to avoid options that reduce overall insulation levels. Achieving very high R-values in our building envelopes should remain a top priority of green design. In most applications, high R-values can be achieved without using high-GWP foams through thoughtful product specification or changes to construction details with little or no increase in construction cost. There remain challenging applications, however, such as sub-slab insulation, where affordable alternatives to XPS simply may not exist or where building officials balk at the alternatives.

In making these product substitutions or altering our construction details to avoid XPS or SPF, we should also pay careful attention to long-term durability. XPS and SPF have some very attractive properties relative to permeability and air barrier performance. In some cases, adding more complex framing systems, such as double-stud framing in residential construction, can create durability problems. If unsure about proper moisture management with new wall systems, seek advice from a knowledgeable building science expert.

For more information:

“Net climatic impact of solid foam insulation produced with halocarbon and non-halocarbon blowing agents” by L.D. Danny Harvey in Building and Environment, August 2007 (Vol. 42, Issue 8)

Inventory of Carbon & Energy (ICE)

Sustainable Energy Research Team

Dept. of Mechanical Engineering,

Univ. of Bath

Bath, U.K.

+44-0-1225-38-4550

www.bath.ac.uk/mech-eng/sert/embodied/

Building Science Corporation

Westford, Massachusetts

978-589-5100

www.buildingscience.com

Continuing Education

Receive continuing education credit for reading this article. The American Institute of Architects (AIA) has approved this course for 1 HSW Learning Unit. The International Living Future Institute (ILFI) has approved this course for 1 CEU.

Learning Objectives

Upon completing this course, participants will be able to:

  1. Define “embodied global warming potential” and “lifetime global warming potential” as they relate to insulation materials.
  2. Describe why some insulations have a longer payback when global warming potential is taken into account.
  3. Describe what this new information about insulation means for building design and construction.
  4. List alternatives to extruded polystyrene and closed-cell spray polyurethane foam insulations.

To earn continuing education credit, make sure you are logged into your personal BuildingGreen account, then read this article and pass this quiz. In addition, to receive continuing education credit for ILFI, please add to the discussion forum on this page by providing a thoughtful comment on the article—for example, its effect on your practice and engagement with Living Building Challenge concepts and petals.

Comments (13)

1 Nice to see the industry is responding posted by Dennis Latta on 05/31/2014 at 09:15 pm

Great insight, and nice to see the industry is trying to create blowing agents with low or no GWP.

2 Avoiding the Global Warming I posted by Tom Hartman on 06/02/2010 at 04:52 am

Thank you Alex.

3 Cost posted by Krysta Aten-Schell on 06/02/2010 at 07:40 am

This is an excellent article, however, our industry always comes down to cost and profit, which of these alternatives are cost-competetive with XPS or SPF?

4 Marginal Payback and Net Clim posted by David White on 06/02/2010 at 08:00 am

Thank you Alex for an excellent and timely article.

I'd like to address the issue of marginal payback analysis. Contrary to many opinions, the approach is not flawed, only misunderstood. In reading Harvey's paper, it is clear that the index of marginal payback simply serves a different purpose than the index of overall payback. The purpose is to identify the R-value at which it is no longer beneficial to add more insulation. Quoting Harvey, page 6: "...the maximum net savings occurs at the RSI-value where the marginal payback time is equal to the lifespan of the insulation."

Thus, knowing the marginal payback time is useful because it tells us how thick is too thick. Overall payback time doesn't do that - we know that we want overall payback to be much shorter than the life span of the building, but how short is short enough? Don't know!

I think that the most useful index would be net life cycle benefit, which is also included to some degree in Harvey's paper. This would give one clear comparison across varying types and thicknesses of insulation (which marginal payback doesn't do as clearly), and designers can then consider that variable in combination with issues of worker, occupant, and public health; cost; durability; etc.

It's also important to emphasize the magnitude of the infiltration load reduction and cooling energy savings that are not included in the analysis - according to Harvey this can as much as double the benefit of the insulation. We do have the tools to assess cooling energy load reduction, and can roughly assess infiltration reduction and compare this to alternative air tightening measures.

5 Air infiltration and influenc posted by John Beeson on 06/03/2010 at 06:07 am

Great article, Alex! Understanding some more of these complexities is so helpful in pushing forward on true environmental dialogue in construction! I just love it. Thanks again.

I'd like to add to David White's comment and poise some questions. If the magnitude of the infiltration load reduction could as much as double the benefit of the insulation, how does this approximately play into the GWP payback charts shown in the article? And the affect of spray foam (average install) vs taping and sealing the joints of board insulation (great install)?

It has always been accepted that the use of spray foams is very beneficial not just for the R-value but also the reduction of air infiltration potential. I just hope we don't make immediate, and perhaps haste, rash decisions to stay away from certain products because of some analysis. Sure, we can use alternatives, especially if they make sense (i.e. cellulose in larger framed structures), but other times, these high GWP materials work well in other aspects that haven't been covered - besides air infiltration, moisture control, perm rating, etc. I'd really like to get a better understanding of the other factors at play here.

6 Insulation value is not God posted by Charles Wahl on 06/03/2010 at 07:13 am

Author concludes, "Achieving very high R-values in our building envelopes should remain a top priority of green design." I don't see why this should go unchallenged. Whether one looks at marginal or total payback, there's obviously a diminishing return for greater insulation values, on an environmental basis. Despite press focus on exceptional projects and practices, most architects are notoriously bad at integrating energy considerations into the design process; instead it's viewed as a regulatory albatross to be endured, a log in the road to visionary design.

Perhaps we need to think hard about ways to build that involve doing the most with the least: expanding the acceptable "comfort zone" for interior conditions, constructing in ways that maximize the effectiveness of less insulation, designing buildings that require super-performing portions to offset their abysmal performance elsewhere -- entropy loves holes and bridges, and exploits them mercilessly.

7 Thanks posted by Tad Everhart on 06/03/2010 at 10:29 pm

Alex and Others, This is very helpful. I'd like to see BASF's XPS ("Styrodur C") included in the comparison. I believe it is foamed with air.

Specifications are at http://www.basf.de/basf2/img/produkte/kunststoffe/styrodur/downloads/EN/...

Of course, until we can persuade BASF to manufacture Styrodur here, the impact of shipping it from Europe may outweigh its benefits.

8 Insulation posted by David Lanfear on 06/05/2010 at 09:17 am

I greatly appreciate this rigorous inquiry as it pertains directly to the material choices we make and recommend to our clients. I am a strawbale builder and in many ways have blown right past much of this debate, but we still use foam in our foundations and in the SIPS we use for roofs. My biggest concern is the foam in ICFS, initially because of the fire retardants, but also because of the embodied energy. Because of that concern we exploring Durisol for our next ICF wall, not only is it effective, is made of waste material and has the added bonus of being manufactured 120 miles from me. Of all the uses for oil, foam insulation,though, might be one of the better ones, at least there is a return on it, unlike the fuel we waste driving to the store for milk, or a movie, or just driving fast because we feel like it.

9 spray foam posted by David Lanfear on 06/05/2010 at 09:22 am

I almost forgot this. Probably most overlooked in the use of spray foam is the difficulty it imposes on future deconstruction. I believe it should be used sparingly for this reason alone.

10 Where to find non-HFC foam in posted by Peter Watson on 09/15/2011 at 12:52 pm

I am involved in a retrofit to an older cottage that involves applying rigid foam insulation to the interior stud face, before the gypsum board, to prevent thermal bridging. I do not know of any non HFC rigid foam product. Does such a product exist or what would you suggest as an alternative product to use in this situation?

11 recommendations posted by Tristan Roberts on 09/15/2011 at 01:05 pm

Peter, please see the table near the end of the article titled 'Avoiding High-GWP Insulation Materials." There is also more discussion of alternatives in the article.

12 Warmer Climates posted by Richard Keleher on 09/27/2013 at 03:08 pm

The article discusses the GWP payback for Boston. In warmer climates, the payback would be even less form the heating side, making the impact of the blowing agents even worse. On the other hand, if air conditioning was included (I believe it was noted that it wasn't), it might push it back the other way. I would like to see an analysis of warmer climates and air conditioning.

13 SPF for Air Sealing in Walls posted by Richard Keleher on 09/27/2013 at 03:14 pm

It was noted that EHDD is switching to using self-adhered flashing to accomplish the air sealing. This is an improvement, because we have found that foam is difficult to install effectively, as noted in the article. But you still need something for insulation, especially for deeper joints, such as at window jambs. We insulate those with foam (since it is not likely to suffer convection currents) but at sills we often use mineral wool, since it will allow accumulated water to drain and it does not soak up water like fiberglass.

Post new comment

Welcome !
*
  • Web page addresses and e-mail addresses turn into links automatically.
  • Lines and paragraphs break automatically.
  • Glossary terms will be automatically marked with links to their descriptions. If there are certain phrases or sections of text that should be excluded from glossary marking and linking, use the special markup, [no-glossary] ... [/no-glossary]. Additionally, these HTML elements will not be scanned: a, abbr, acronym, code, pre.